UNITED STATES COAST GUARD CIVIL ENGINEERING UNIT CLEVELAND 1240 EAST NINTH STREET CLEVELAND, OHIO 44199-2060 USCG Contract No. HSCG83-07-D-3WF172 USCG Task Order No. HSCG83-10-J-PCU005 STRUCTURAL INSPECTION AND ASSESSMENT OF THE U.S. COAST GUARD FRYING PAN SHOALS LIGHT STATION Location: CAPE FEAR, NORTH CAROLINA P/N 2705210 JANUARY 2010 STRUCTURAL INSPECTION AND ASSESSMENT OF THE U.S. COAST GUARD FRYING PAN SHOALS LIGHT STATION IN THE ATLANTIC OCEAN 32.5 MILES SOUTHEAST OF CAPE FEAR, NORTH CAROLINA JANUARY 2010 Prepared For: UNITED STATES COAST GUARD CIVIL ENGINEERING UNIT CLEVELAND COLLINS JOB 6277-40 EXECUTIVE SUMMARY Collins Engineers, Inc., as a subconsultant to Michael Baker Jr., Inc., under contract with CEU Cleveland, was issued a task order to perform a structural inspection of the Frying Pan Shoals Light Station. A field inspection was performed on January 5, 2010, during which a three person team consisting of professional engineers conducted a visual and tactile examination of the accessible structural steel members. Overall, the primary structural elements were in satisfactory condition with members exhibiting some minor section loss and minor deterioration. The steel pipe piles, steel bracing, and the primary steel girders and W Sections that provide the load resisting system for the structure exhibited minor to moderate deterioration above the splash zone. Loss of paint coating, corrosion, and pack rust was evident on most structural elements exposed to the marine environment. No significant loss of steel section was observed on these components. Within the splash zone, the piles exhibited a thick layer of corrosion and rust nodules. This area was inaccessible for a hands-on view at the time of the inspection and the extent and severity of the deterioration on the piles between the splash zone and the channel bottom was unable to be evaluated. In general, the Helicopter Deck was in satisfactory condition with only minor surface corrosion throughout and moderate corrosion isolated to areas around the exterior door opening and Light Tower stairway in the Generator Room. The Light Tower stairway was in satisfactory condition with failing paint and minor surface corrosion. The Helicopter Deck walkways have some minor to moderate deterioration of the support beams, channels, and grating with isolated areas of advanced loss of section. When compared to the available plans from Chesapeake Light, the Helicopter Deck framing is similar but not identical. The Machinery and Quarters Deck was generally in satisfactory condition. The columns, wall panels, and wall framing that were visible had some minor deterioration such as failure of paint coatings and minor surface corrosion. The interior floors felt stable with no visible signs of excessive deformations or movement during the inspection. The Machinery and Quarters Deck walkways had some minor to moderate deterioration of the support beams, channels, and grating with isolated areas of advanced loss of section. The main beams and girders supporting the Machinery and Quarters Deck were observed from the Maintenance Deck. These structural elements were exposed to the marine environment and exhibited significant corrosion and pack rust. Due to the limited access to the deck support members, the i extent and severity of this deterioration could not safely be evaluated during this inspection. From the limited accessible areas, this deterioration appeared to have some minor section loss which does not appear to have affected the structural capacity of the members. The Maintenance Deck was completely exposed to the marine environment and had the most significant deterioration. Due to the advanced deterioration of the access walkways, an evaluation of this deck could only be made from the North and South stairwells leading from the Machinery and Quarters Deck. Overall, the Maintenance Deck was in serious to poor condition. The storage tanks hanging below the Quarters Deck exhibited significant corrosion with some section loss. A majority of the walkway had advanced section loss of the beams, channels, grating, and handrails which has seriously affected its structural capacity and safety. This deck was unsafe and access to this area should be restricted. Due to limited access, the main structural legs and jackets supporting Frying Pan Shoals Light were inspected from the Maintenance Deck. The piles were generally in fair condition. The main piles, jackets, and diagonal bracing appeared to have light to moderate corrosion with concentrated corrosion around the splash zone. There were no signs of distortions or abnormal deformations of these members. The boat landing was completely deteriorated and all access ladders, stairs, and walkways near the water were unfit for use. Access by boat was not possible. Recommended repairs to the structure would include thoroughly cleansing and reapplying a protective coating suitable for marine environments, rebuilding the entire walkways for the Maintenance Deck, and replacing the support members for the walkways at specific locations throughout the Helicopter and Machinery and Quarters Deck. After completion of the above recommendations, it is recommended that the Frying Pan Light Station be inspected to insure proper implementation of the corrective measures. It is also recommended that the above water portions of the Light Station be inspected at an interval not to exceed 24 months. An underwater inspection of the portions of the piles and pile bracing members below the surface of water should be performed prior to implementation of any significant superstructure repairs. The estimated cost to provide the recommended repairs is $1,375,000. A detailed cost estimate for the repairs is located in Appendix C. ii TABLE OF CONTENTS Page EXECUTIVE SUMMARY ..........................................................................i TABLE OF CONTENTS .......................................................................... iii 1.0 INTRODUCTION .......................................................................... 1 1.1 Purpose and Scope ............................................................... 1 1.2 General Description of the Structure ....................................... 1 1.2.1 Description of Helicopter Deck .......................................... 1 1.2.2 Description of Machinery and Quarters Deck....................... 2 1.2.3 Description of Maintenance Deck and Piles......................... 2 1.3 Method of Investigation ........................................................ 3 1.4 Data Collection .................................................................... 3 2.0 OBSERVED CONDITIONS ............................................................. 3 2.1 Helicopter Deck.................................................................... 4 2.2 Machinery and Quarters Deck ................................................ 4 2.3 Maintenance Deck and Piles .................................................. 5 3.0 ASSESMENT.............................................................................. 6 3.1 Helicopter Deck.................................................................... 6 3.2 Machinery and Quarters Deck ................................................ 6 3.3 Maintenance Deck ................................................................ 7 4.0 RECOMMENDATIONS................................................................. 7 4.1 Helicopter Deck.................................................................... 7 4.2 Machinery and Quarters Deck ................................................ 7 4.3 Maintenance Deck ................................................................ 8 4.4 Piles.................................................................................... 8 4.5 Re-Inspection Frequency ....................................................... 8 5.0 COST ESTIMATE........................................................................ 9 iii Appendix A – Figures Figure 1. Location Map Figure 2. General Elevation Figure 3. Helicopter Deck Plan Figure 4. Machinery and Quarters Deck Plan Figure 5. Maintenance Deck and Piles Plan APPENDIX B – PHOTOGRAPHS Photograph 1. Overall View of Light Station, Looking West. Photograph 2. Overall View of Light Station, Looking East. Photograph 3. Overall View of Light Station, Looking North. Photograph 4. Overall View of Light Station, Looking South. Photograph 5. View of the Helicopter Deck from the Light Tower, Looking Northwest. Photograph 6. Floor-Level View of the Helicopter Deck, Looking East. Photograph 7. View of Typical Support Beam of the Helicopter Deck. Note the Minor Coating Failure and Surface Corrosion at the Beam/ Decking Interface. Photograph 8. View of Support Beam of the Helicopter Deck Walkway with an Isolated Area of Section Loss. Photograph 9. View of Support Structure of the Helicopter Deck Walkway showing Typical Overall Condition. Photograph 10. View of the East Fascia of the Helicopter Deck Walkway, Looking North. Photograph 11. View of the West Fascia of the Helicopter Deck Walkway, Looking South. Photograph 12. View of the Light Tower Looking Up from the Base. Photograph 13. View of the Stairway in the Light Tower Looking Up. iv Photograph 14. Photograph 15. Photograph 16. Photograph 17. Photograph 18. Photograph 20. Photograph 21. Photograph 22. Photograph 23. Photograph 24. Photograph 25. Photograph 26. Photograph 27. Photograph 28. Photograph 29. Photograph 30. Photograph 31. View of the Stairway in the Light Tower Looking Up showing Protective Coating Failing on the Stairs. Overall View of the Light Tower from the Helicopter Deck, Looking South. View of the Light Tower Stairway, Looking Down. View of the Light inside of the Light Tower. View of the Light Tower Windows with several broken or intact with bullet holes. View of the Generator Storage Area with Floor Delamination. View of Typical Floor Delamination near the access door. View of the Electrical Cabinets and Fuel Storage in Generator Room. View of the Recreation Room, Looking Northeast View of the Recreation Room’s main area, Looking West. View of the Galley, Looking North. View of the Galley, Looking South. View of the General Storage, Looking North. View of the General Storage, Looking East. View of the Living Quarters Bathroom from Hallway, Looking Northeast. View of the Living Quarters Bathroom, Looking Northwest View of the Radio Room from the Living Quarters Hallway, Looking East. Photograph 32. View of the Radio Room, Looking Southeast. v Photograph 33. View of an Office adjacent to the Radio Room, Looking East. Photograph 34. View looking into Room No. 1 with Paint Failing on the Walls, Looking West. Photograph 35. View looking into Room No. 2 with Paint Failing on the Walls, Looking West. Photograph 36. View of the East Fascia and Exterior Platform and Generator Access Door, Looking North Photograph 37. View of the East Fascia at the East/West Hallway Access, Looking North Photograph 38. View of the West Fascia looking toward the Southwest Corner at the East/West Hallway, Looking South. Photograph 39. View of the Access Platform Aligned with the East/West Hallway, Looking South Photograph 40. View of the Maintenance Level, Looking South. Photograph 41. View of the Maintenance Level, Looking East. Photograph 42. View of Protective Coating Loss that is Typical on all support members. Photograph 43. View of Floor Pan of the Living Quarters with Heavy Pitting. Photograph 44. View of the Underside of the Storage Tanks with Severe Corrosion. Photograph 45. View of the Maintenance Level Walkway with Section Loss. Photograph 46. View of the Maintenance Level Walkway with New Grating over Deteriorated Grating. Photograph 47. Close-up View of Severely Deteriorated Floor Grating that has given way. vi Photograph 48. View of Severely Corroded Stairway from the Machinery and Quarters Deck to the Maintenance Deck. Photograph 49. View of the Piles and Diagonal Braces on the Southwest corner of Structure. Photograph 50. View of the Piles and Diagonal Braces on the Southeast corner of Structure. Photograph 51. View of the Piles and Support Beams on the Northeast corner of Structure. Photograph 52. View of the Piles and Access Stairs on the Northwest corner of Structure. Photograph 53. View of Severely Deteriorated Walkway on the Cross- Bracing near the Waterline. APPENDIX C – COST ESTIMATE APPENDIX D – REFERENCED DESIGN PLANS vii 1.0 INTRODUCTION 1.1 Purpose and Scope The purpose of this project was to perform a condition assessment of the existing condition of the above water portions of Frying Pan Shoals Light Station, located 32.5 miles southeast of Cape Fear, North Carolina. Collins Engineers, Inc. (Collins) conducted the site inspection for the USCG Civil Engineering Unit, Cleveland (CEU Cleveland) on January 5, 2010. The point of contact at CEU Cleveland was LT Neil Orlich at (216) 902-6249. The scope of work included an inspection of the structural elements supporting the structure. Photographs, video and field notes were taken to record the condition of the structural elements at the time of inspection. Design plans were not available for this structure; however, design plans dated August 3, 1964 were available for the Chesapeake Light Station. The plans were typically consistent with the Frying Pan Shoals Light Station layout. Based on the inspection findings, repair recommendations, which included the type, estimated cost, and suggested timetable of repair work were included. 1.2 General Description of the Structure The US Coast Guard Frying Pan Shoals Light Station is located in the Atlantic Ocean at approximately 32.5 miles southeast of Cape Fear, North Carolina. The coordinates of the light are 35°29'00”N, 77°35'00"W. The structure was constructed with a design which is commonly referred to as a “Texas Tower”. The structure consists of a light tower, Helicopter Deck, Machinery and Quarters Deck, and Maintenance Deck. The decks are supported by four steel pipe piles with intermediate horizontal bracing. The structure was originally designed and constructed with a boat landing, which is no longer in place. Refer to Photographs 1 through 4 in Appendix B for typical views of the structure. Refer to Figure 1 in Appendix A for location map of the facility, and Figures 2 and 3 in Appendix A for a general elevation view of the structure. 1.2.1 Description of the Helicopter Deck The Helicopter Deck is approximately a 77-foot by 77-foot square with a 7-foot by 7-foot by approximately 30-foot tall tower located at the southeast corner of the structure. A steel grating walkway extends around the entire Helicopter Deck. The Helicopter Deck is comprised of a steel plate 1 deck which is supported by ST-shape floor stingers on W-shape floor beams. The Helicopter Deck floor beams are welded to 8-inch by 8-inch hollow structural steel columns. The columns are generally ordered in 6 rows of 6 columns, with additional columns located around the tower section in the southeast corner. Columns extend from the Machinery and Quarters Deck (base of column) to the Helicopter Deck (top of column). 1.2.2 Description of the Machinery and Quarters Deck The Machinery and Quarters Deck is located below the Helicopter Deck. Based on similar plans from Chesapeake Light the Machinery and Quarters Deck consists of steel plates supported by ST-shape floor stingers on W-shaped floor beams. The Machinery and Quarters Deck floor beams are supported by plate girders. There are four 5-foot deep plate girders oriented east-west which span the entire width of the structure. Large storage tanks are connected to these girders. There are a total of eleven 4foot- deep plate girders oriented north-south which span between the 5-foot deep plate girders. The ends of the plate girders are welded to four W-shape girders which span from pile cap to pile cap. Columns extend from the Machinery and Quarters Deck (base of column) to the Helicopter Deck (top of column). 1.2.3 Description of the Maintenance Deck and Piles The Maintenance Deck lies below the Machinery and Quarters Deck. It primarily consists of a steel grating floor supported by various steel W- shapes and channels. Two sets of stairs, one at the northwest corner and one at the southwest corner, connect this deck with the Machinery and Quarters Deck. A third set of stairs extends down to the Maintenance Deck from the main passageway in the Machinery and Quarters Deck. Only the upper portions of a spiral staircase on the northwest pile remain intact. The piles are constructed of steel pipe sections. From the available plans, the piles are labeled 1, 2, 3, and 4 clockwise starting at the northeast pile. Horizontal bracing members, consisting of steel pipe sections, were located approximately 10 ft above the waterline at the time of the inspection. Diagonal foundation bracing members, also consisting of steel pipe sections, span vertically from the piles to the horizontal braces as well as horizontally from horizontal brace to horizontal brace. 2 1.3 Method of Investigation A detailed visual and tactile inspection was conducted to determine the physical condition of the above water portions of the light station. A three-person team consisting of licensed professional engineers performed the inspection. The station was accessed via a chartered helicopter (Bell Long Ranger) through Helo Air, Inc. The inspection consisted of a Level I visual and tactile examination of all accessible components of the structure. Particular attention was given to any noted areas of excessive deterioration or apparent distress. For inspection documentation, the structure was divided into the Helicopter Deck, the Machinery and Quarters Deck, and the Maintenance Deck. The Helicopter Deck includes the Light Tower and the Helicopter Deck supporting floor beams, girders, and columns. The Machinery and Quarters Deck includes the supporting Quarters Deck floor beams and girders, the superstructure plate girders, and the top-of-pile girders. The Maintenance Deck, includes the Maintenance Deck walkway, the walkway supporting members, the above water portions of the four piles, and the pile bracing members. 1.4 Data Collection A biennial inspection dated June 1996 was available during the inspection. Design plans were not available for the Frying Pan Shoals Light Station; however, the plans for the Chesapeake Light Station were very similar to the construction of the Frying Pan Shoals Light Station. The following design drawings were obtained from CEU Cleveland: Plans Drawing Number Sheets Chesapeake Light Station (Design) 109001 1-50 Refer to Appendix D for copies of the design drawings referenced for the assessment report. 2.0 OBSERVED CONDITIONS The following criteria govern the assessment ratings of the structural components of the light station: -Very Good Condition – no problems noted. 3 -Good Condition – some minor problems. -Satisfactory Condition – structural elements show some minor deterioration. -Fair Condition – all primary structural elements are sound but may have minor section loss, cracking, or spalling. -Poor Condition – advanced section loss, deterioration, or spalling. -Serious Condition – loss of section, deterioration, or spalling has seriously affected primary structural components. Local failures are possible. 2.1 Helicopter Deck Overall, the structural elements of the Helicopter Deck were in satisfactory condition. The top of the Helicopter Deck exhibited minor coating failure with minor corrosion covering approximately 20 percent of the surface area. The underdeck support members were in satisfactory condition with minor surface corrosion in sporadic areas. Moderate surface corrosion with some minor loss of section was primarily isolated to areas around the external door openings and on the stairway to the Light Tower in the Generator Room. The walkway extending around the perimeter of the Helicopter Deck exhibited light to moderate corrosion and was in fair condition. The walkway grating was typically intact and exhibited light to moderate corrosion. The steel support members for the Helicopter Deck walkway exhibited a loss of protective coating with moderate corrosion and random isolated areas of section loss. The Light Tower located on the Helicopter Deck was in satisfactory condition. Light to moderate corrosion was observed on all exposed steel surfaces and covered approximately 90 percent of the surface area. There was no significant sign of distress or section loss on the structural members of the Light Tower. Refer to Photographs 5 through 118 in Appendix B for views of the deficiencies observed on the Helicopter Deck. 2.2 Machinery and Quarters Deck Overall, the primary structural elements within the Machinery and Quarters Deck were in satisfactory condition. The visible structural elements including the exterior wall tube members, the wall panels, and the interior columns exhibited minor deterioration in the form of paint failure and light to moderate surface corrosion. The exposed steel plate floor in the Generator Room had light to moderate corrosion throughout with rust nodules up to 1 4 in. in diameter and minor delamination of the plate. In the other locations the deck had a raised sub floor with linoleum tiles. Furniture, tools, and equipment still remained throughout the entire Machinery and Quarters Deck. Access was limited on the Maintenance Deck because the walkways were unsafe, therefore, only isolated portions of the steel support members for the Machinery and Quarters Deck could be inspected. Parts of the underside of the Machinery and Quarters Deck were accessed by the walkway stairs on the north and south fascias and other portions were visible from the interior stairs in the main passageway. The accessible portions of the deep plate girders and W sections typically exhibited a loss of protective coating with moderate to heavy corrosion and scale with minor loss of section. The walkway surrounding the Machinery and Quarters Deck was in fair condition. The walkway grating was typically intact and exhibited light to moderate corrosion. The steel support members for the Machinery and Quarters Deck walkway exhibited a loss of protective coating with moderate corrosion and random isolated areas of section loss. Refer to Photographs 19 through 40 in Appendix B for views of the deficiencies observed in the Machinery and Quarters Deck. 2.3 Maintenance Deck and Piles Overall, the accessible structural elements within the Maintenance Deck were in poor to serious condition. Due to the heavy deterioration of the steel grating for the Maintenance Deck, a majority of these elements were inaccessible. The inspectors were able to view the Machinery Deck and Piles from the bottom of the exterior stairwell on the north and south faces of the structure and from the interior stairwell located in the center of the structure but did not attempt to walk on the gratings with considerable loss of section. The steel grating was heavily deteriorated and exhibited up to 100 percent loss of section. Several sections of grating were missing and temporary grating was installed in isolated locations. The steel support members for the walkway were heavily deteriorated and exhibited up to 100 percent loss of section. Since walkways to the lower portions of the piles were no longer present, only the upper portions of the piles were accessible for close inspection. With a zoom lens, all four piles were observed to have a loss of protective coating and minor surface corrosion on up to 100 percent of the surface areas above the splash zone. Within the splash zone the piles exhibited heavier corrosion with rust nodules and scaling. The diagonal pile bracing members above the waterline exhibited a loss of protective coating 5 and minor surface corrosion on up to 100 percent of the surface area. The spiral stairwell on the Pile No. 2 was heavily deteriorated with up to 100 percent loss of section. Refer to Photographs 41 through 52 in Appendix B for views of the deficiencies observed on the Maintenance Deck and Piles. 3.0 ASSESSMENT 3.1 Helicopter Deck Overall, the Helicopter Deck was in satisfactory condition. The areas of coating loss and surface corrosion on the members supporting the Helicopter Deck are generally minor with no appreciable loss of section, and as a result, are not structural concerns at this time. From the observed conditions, there were no indications that the Helicopter Deck should be restricted from its intended use. The walkway surrounding the Helicopter Deck showed some signs of distress with moderate corrosion only in isolated locations of the floor grating and support members. The Helicopter Deck transfers load down through the 8x8 columns to the W24 beams in the Machinery and Quarters Deck. The load is then carried down to the structural legs through the 5 foot deep girders. There were no observed deficiencies in the Helicopter Deck that would result in a reduction in the designed load capacity. However, these loads are transferred down to the W24 beams which ultimately support the entire Helicopter Deck in the Machinery and Quarters Deck. Due to the significant deterioration of the Maintenance Deck walkways, the extent and severity of the deterioration of the underside of the Machinery and Quarters Deck, including the W24 beams, could not be fully documented. Based on the observed conditions of the assessable areas of the W24 beams, the minor to moderate deterioration should not have reduced the structurally capacity significantly. However, without a structural load rating and positive confirmation of the extent of the deterioration of the W24 beam, we cannot definitively determine that a helicopter could land on the Helicopter Deck. The inspection team landed a Bell Long Ranger weighing approximately 4000 pounds fully loaded. The pilot kept the helicopter fully running in order to reduce the weight applied to the deck. 3.2 Machinery and Quarters Deck The corrosion on the girders and beams supporting the Machinery and Quarters Deck has probably been accelerated by the members’ close proximity to salt water spray and the corrosive air environment. The loss of 6 protective coating observed on a majority of the members has also accelerated this corrosion. The majority of the members supporting the deck exhibited loss of protective coating and minor to moderate surface corrosion. Heavy corrosion was observed in the bottom flanges of the majority of the inspected girders. The walkway surrounding the Quarters and Machinery Deck showed some signs of distress with moderate corrosion only in isolated locations of the floor grating and support members. 3.3 Maintenance Deck and Piles Overall, the Maintenance Deck was unusable at the time of the inspection. The heavy deterioration of the steel support members and steel grating has rendered the Maintenance Deck unsafe for use. The corrosion on the upper portions of the piles and pile braces appeared to be limited to the surface, with no appreciable loss of section. Given that the heaviest corrosion was observed near the waterline, an overall structural assessment of the piles cannot be determined until the piles are closely inspected at and below the waterline. The spiral staircase located on the northwest pile was deteriorated to the point where it was unsafe for use. 4.0 RECOMMENDATIONS 4.1 Helicopter Deck All exposed steel surfaces including the decking, the deck support members, and Light Tower support members should be thoroughly cleaned and recoated with a coating manufactured specifically for marine environments. As part of this process, any areas of surface corrosion should be blasted clean to bare metal prior to the application of the protective coating. The random isolated areas of section loss in the grating and support members should be replaced prior to returning the Light Station to service. 4.2 Machinery and Quarters Deck All of the exposed steel surfaces located on the internal portions of the Machinery and Quarters Deck should be thoroughly cleaned and recoated using a coating specifically manufactured for marine environments. 7 Primary deck and structural support members should be thoroughly cleaned and recoated using a coating specifically manufactured for marine environments. The random isolated areas of section loss in the grating and support members should be replaced prior to returning the Light Station to service. 4.3 Maintenance Deck Due to the significant deterioration it is recommended that a complete replacement of the Maintenance Deck be performed before returning the Light Station to service. This would include a complete replacement of the steel grating support members, the steel grating, and the steel handrails. As part of this repair, consideration should be given to installing a new stairwell below the Maintenance Deck and a boat landing so that the structure is accessible from the water. 4.4 Piles Because there was no documentation of a previous underwater inspection available, a thorough inspection of the piles and pile bracing members below water should be performed prior to any repair or rehabilitation work being performed on the superstructure. The purpose of the inspection should be to document the condition of the piles and bracing members and determine if the piles provide adequate support for the superstructure and its anticipated loads. Pending the underwater investigation, consideration should be given to installing a cathodic protection system on the piles to prolong their serviceable life. The portions of the piles and pile bracing above the waterline should be thoroughly cleaned and recoated with a coating manufactured specifically for marine applications. 4.5 Re-Inspection Frequency It is recommended that the above water structural steel elements be inspected at an interval not to exceed 24 months. It is also recommended that an underwater inspection of the piles and pile bracing be performed within the next six months, and at intervals not to exceed 5 years. 8 5.0 COST ESTIMATE The following figure is a rough order of magnitude cost estimate to be used for planning purposes and to identify preliminary budgetary numbers only. This cost does not represent a specific detailed scope of work, timetable, escalation pricing, or specific prevailing wage rates. A detailed scope of work and completed structural drawings are required to determine more accurate construction costs. It is estimated that the total cost to perform the recommended repairs is approximately $1,375,000. Refer to Appendix C for a detailed cost estimate. Respectfully submitted, COLLINS ENGINEERS, INC. Thai G. Trinh, P.E. 9 APPENDIX A – FIGURES APPENDIX B – PHOTOGRAPHS Photograph 1. Overall View of Light Station, Looking West. Photograph 2. Overall View of Light Station, Looking East. Photograph 3. Overall View of Light Station, Looking North. Photograph 4. Overall View of Light Station, Looking South. Photograph 5. View of the Helicopter Deck from the Light Tower, Looking Northwest. Photograph 6. Floor-Level View of the Helicopter Deck, Looking East. Photograph 7. View of Typical Support Beam of the Helicopter Deck. Note the Minor Coating Failure and Surface Corrosion at the Beam/ Decking Interface. Photograph 8. View of Support Beam of the Helicopter Deck Walkway with an Isolated Area of Section Loss. Photograph 9. View of Support Structure of the Helicopter Deck Walkway showing Typical Overall Condition. Photograph 10. View of the East Fascia of the Helicopter Deck Walkway, Looking North. Photograph 11. View of the West Fascia of the Helicopter Deck Walkway, Looking South. Photograph 12. View of the Light Tower Looking Up from the Base. Photograph 13. View of the Stairway in the Light Tower Looking Up. Photograph 14. View of the Stairway in the Light Tower Looking Up showing Protective Coating Failing on the Stairs. Photograph 15. Overall View of the Light Tower from the Helicopter Deck, Looking South. Photograph 16. View of the Light Tower Stairway, Looking Down. Photograph 17. View of the Light inside of the Light Tower. Photograph 18. View of the Light Tower Windows with several broken or intact with bullet holes. Photograph 20. View of the Generator Storage Area with Floor Delamination. Photograph 21. View of Typical Floor Delamination near the access door. Photograph 22. View of the Electrical Cabinets and Fuel Storage in Generator Room. Photograph 23. View of the Recreation Room, Looking Northeast Photograph 24. View of the Recreation Room’s main area, Looking West. Photograph 25. View of the Galley, Looking North. Photograph 26. View of the Galley, Looking South. Photograph 27. View of the General Storage, Looking North. Photograph 28. View of the General Storage, Looking East. Photograph 29. View of the Living Quarters Bathroom from Hallway, Looking Northeast. Photograph 30. View of the Living Quarters Bathroom, Looking Northwest Photograph 31. View of the Radio Room from the Living Quarters Hallway, Looking East. Photograph 32. View of the Radio Room, Looking Southeast. Photograph 33. View of an Office adjacent to the Radio Room, Looking East. Photograph 34. View looking into Room No. 1 with Paint Failing on the Walls, Looking West. Photograph 35. View looking into Room No. 2 with Paint Failing on the Walls, Looking West. Photograph 36. View of the East Fascia and Exterior Platform and Generator Access Door, Looking North Photograph 37. View of the East Fascia at the East/West Hallway Access, Looking North Photograph 38. View of the West Fascia looking toward the Southwest Corner at the East/West Hallway, Looking South. Photograph 39. View of the Access Platform Aligned with the East/West Hallway, Looking South Photograph 40. View of the Maintenance Level, Looking South. Photograph 41. View of the Maintenance Level, Looking East. Photograph 42. View of Protective Coating Loss that is Typical on all support members. Photograph 43. View of Floor Pan of the Living Quarters with Heavy Pitting. Photograph 44. View of the Underside of the Storage Tanks with Severe Corrosion. Photograph 45. View of the Maintenance Level Walkway with Section Loss. Photograph 46. View of the Maintenance Level Walkway with New Grating over Deteriorated Grating. Photograph 47. Close-up View of Severely Deteriorated Floor Grating that has given way. Photograph 48. View of Severely Corroded Stairway from the Machinery and Quarters Deck to the Maintenance Deck. Photograph 49. View of the Piles and Diagonal Braces on the Southwest corner of Structure. Photograph 50. View of the Piles and Diagonal Braces on the Southeast corner of Structure. Photograph 51. View of the Piles and Support Beams on the Northeast corner of Structure. Photograph 52. View of the Piles and Access Stairs on the Northwest corner of Structure. Photograph 53. View of Severely Deteriorated Walkway on the Cross-Bracing near the Waterline. APPENDIX C – COST ESTIMATE COST ESTIMATE DATE PREPARED January 19, 2010 SHEET OF 1 1 ACTIVITY AND LOCATION United States Coast Guard Frying Pan Shoals Light Station Repair (Texas Tower Platform) DESIGN/ENGINEERING CONTRACT NO. HSCG83-07-D-3WF172 IDENTIFICATION NUMBER 0 ESTIMATED BY TGT CATEGORY CODE NUMBER PROJECT TITLE USCG Frying Pan Shoals Light Station Structural Assessment General Conditions STATUS OF DESIGN Planning Level Estimate JOB ORDER NUMBER HSCG83-10-J-PCU004 ITEM DESCRIPTION QUANTITY MATERIAL COST LABOR COST EQUIPMENT COST ENGINEERING ESTIMATE NUMBER UNIT UNIT COST TOTAL UNIT COST TOTAL UNIT COST TOTAL UNIT COST TOTAL Mobilization Jack-Up Vessel Helicopter Deck Clean & Coat Steel Demolish Portion of Walkway Replace Portion of Walkway Machinery & Quarters Deck Clean & Coat Steel Demolish Portion of Walkway Replace Portion of Walkway Machinery & Quarters Deck Demolish Walkway Clean & Coat Steel Replace Walkway Replace Boat Landing Cathodic Protection 1 LS 75 Days 7333 SF 1 LS 2260 LBS 7100 SF 1 LS 2260 LBS 1 LS 3870 SF 40000 LBS 27000 LBS 8 EA 34,000 34,000 10,000 750,000 $4.50 32,999 10,000 10,000 $2.50 5,650 $4.50 31,950 10,000 10,000 $2.50 5,650 35,000 35,000 $4.50 17,415 $2.50 100,000 $2.50 67,500 3,000 24,000 Subtotal $0.00 $0.00 $0.00 $1,124,163.50 Profit @ 10% Contingencies @ 10% $112,416.35 $112,416.35 Total $1,348,996.20 Bonding @ 2% Total $26,979.92 $1,375,976.12 APPENDIX D – REFERENCED DESIGN PLANS